Rod type
Pre Rod filter is a primary stage pre filter used commonly in stand alone system, AHU and other HVAC applications. The synthetic filter media with HDPE mesh on both side is supported by Rods provide rigid structure to the filter. This construction of the filter makes it lightweight and easy to handle.
Filter Specifications and Performance
Below are the detailed specifications and performance matrix for our Rod Type
Standard Sizes Panel (HxWxD) | Air Flow (CFM) | Pressure Drop Initial (mm WG) | Pressure Drop Final (mm WG) | Avg. Arrestance (EU3) | Avg. Arrestance (EU4) | Test Method/Std. |
---|---|---|---|---|---|---|
610x610x50 | 2000 | ≤8.5 | 20 | 80-90% (Filter equivalent to MERV 7) | >90% (Approx arrestance >90% at 10 micron.) ( Filter equivalent to MERV 8) | Type Tested As Per ASHRAE 52.1/ EN779 |
610x305x50 | 1000 | ≤8.5 | 20 | |||
305x610x50 | 1000 | ≤8.5 | 20 | |||
305x305x50 | 500 | ≤8.5 | 20 | |||
610x610x305 | 2000 | ≤8 | 25 | |||
610x305x305 | 1000 | ≤8 | 25 | |||
305x610x305 | 1000 | ≤8 | 25 | |||
305x305x305 | 500 | ≤8 | 25 |
Filter Construction Options
Explore our standard construction features and available customization options to meet your specific filtration needs
Constructions | Standard | Customization Options |
---|---|---|
Filter Media | Nonwoven Synthetic | Fire Retardant Media |
Frame Material | Aluminum Section | GI/SS304/SS316 |
Media Support/ Separator | GI Rod | SS Rod |
Frame Type | Box/ Flange | |
Operating Temp. | 60°C | |
Sealant | Epoxy Resin | |
Gasket | P.E. Foam | Neoprene / Silicon / Nitrile |
Air Flow Direction | Flange To Cassette | Cassette to Flange |
Get in Touch for Customized Solutions
Contact us now to find out how we can customize our filters for you.